Ventilation hygiene in the UK

UK special: TR19 Air

  • LET40 inlet funnel at a ceiling supply air outlet
  • MBASS30V3 with transverse adapter and inlet nozzle
  • MBASS30V3 with LKS100 air sampling head
   

Where are you sampling? At a ceiling diffuser, the LET40 inlet funnel collects supply air for the MBASS30V3 with the LKS100 sampling head. Inside a ventilation duct, use the transverse adapter and an inlet nozzle matched to the local air velocity. Agree the sampling location with the client before investigating a complaint or assessing conditions after maintenance.

MBASS30V3 equipment at a glance

Sampling location Equipment
Supply air terminal MBASS30V3 with LKS100 and LET40 inlet funnel. Add the Stativ366 tripod for elevated outlets as needed.
Inside a ventilation duct MBASS30V3 with LKS100, transverse adapter and an inlet nozzle selected for the local air velocity.

What does air sampling add to a TR19 Air inspection?

BESA’s March 2026 edition of TR19 Air covers inspection, cleaning and verification of internal ductwork cleanliness. A culture result describes the air sampled at a particular place and time. Duct cleanliness is assessed using the inspection and verification methods specified for the project. Where a project also calls for microbiological evidence, agree the sampling locations, comparison sample and interpretation with the client and laboratory. Record the operating condition of the system so the results can be related to the inspection findings.

Sampling supply air at a ceiling diffuser

The MBASS30V3 air sampling system provides the airflow and the LKS100 sampling head deposits airborne particles onto a culture medium for a count of culturable microorganisms. At a ceiling diffuser, the LET40 inlet funnel lets the operator position the intake at the supply outlet. Check that the outlet is delivering sufficient air for the sample. If room air enters the funnel, the result can no longer be attributed solely to the supply air.

The Stativ366 telescopic tripod supports the instrument beneath elevated outlets. Its maximum working height is 3.66 m. With the MBASS30V3 and LET40 mounted, the funnel reaches above 4 m. Check the available floor space, outlet dimensions and access when planning the visit.

Selecting an inlet nozzle for in-duct air sampling

For an in-duct sample, the LKS100 takes a transverse adapter with an inlet nozzle. The nozzle selection depends on the air velocity at the sampling point and the sampling head in use. Provide those details when specifying the equipment for isokinetic sampling. Record the position in the duct so it can be found again during a follow-up inspection.

What does the laboratory report?

The laboratory incubates the collected samples and reports colonies recovered under the agreed culture conditions. Agree on the medium, transport arrangements and reporting units before attending site. If the assessment calls for comparison with outdoor or room air, document the reference location and use a comparable method.

Planning a ventilation survey? Tell us whether you are sampling at a diffuser or in a duct, the access height or local air velocity, and which sampling head you already use. Request advice on your MBASS30V3 configuration.

Download the LKS100 and PS 30 data sheet (PDF). Further reading: BESA TR19 Air, LET40 operating instructions and Stativ366 data sheet.